來源網(wǎng)絡(luò)
設(shè)備 Equipment | 周期 Interval | 檢查要求 Outline of Requirement | 規(guī)則出處 Guideline |
手提滅火器 Portable fire extinguishers | Annually | Inspections in accordance with the manufacturer’s instructions, etc. | Res.A.951(23), para.9.1 |
5-yearly | Discharged as part of fire drills, etc. | Res.A.951(23), para.9.1.1 | |
10-yearly | Hydrostatic test | Res.A.951(23), para.9.1.2 | |
舟車式滅火器 Wheeled (mobile) fire extinguishers | Monthly | Verification in place, etc. | MSC.1/Circ.1432, para.5.9 |
Annually | Inspections in accordance with manufacturer’s instructions, etc. | MSC.1/Circ.1432, para.7.12 | |
5-yearly | Visual inspection, etc. | MSC.1/Circ.1432, para.9.6 | |
10-yearly | Hydrostatic test | MSC.1/Circ.1432, para.10.5 | |
手提泡沫噴射器 Portable foam applicator units | Monthly | Inspections in accordance with manufacturer’s instructions, etc. | MSC.1/Circ.1432, para.5.8 |
Annually | foam control test, etc. | MSC.1/Circ.1432, para.7.11 | |
固定二氧化碳系統(tǒng) Fixed CO2 fire-extinguishing systems | Monthly | Verification of each part, etc. | MSC.1/Circ.1318, para.4 |
Annually | Visual inspection, etc. | MSC.1/Circ.1318, para.5 | |
2.5-yearly | Verification of contents, etc. | MSC.1/Circ.1318, para.6.1 | |
5-yearly | Operation test, etc. | MSC.1/Circ.1318, para.6.2 | |
10-yearly | Hydrostatic test, etc. | MSC.1/Circ.1318, para.6.1 | |
固定干粉系統(tǒng) Fixed dry chemical powder systems | Monthly | Verification of valves and gauges, etc. | MSC.1/Circ.1432, para.5.6 |
Annually | Visual inspection, etc. | MSC.1/Circ.1432, para.7.9 | |
2-yearly | Testing a sample of dry chemical powder, etc. | MSC.1/Circ.1432, para.8.2 | |
10-yearly | Hydrostatic test or Non-destructive test | MSC.1/Circ.1432, para.10.3 | |
固定泡沫系統(tǒng) Fixed foam fire-extinguishing systems | Monthly | Verification of valves and gauges, etc. | MSC.1/Circ.1432, para.5.3 |
Quarterly | Verification of quantity of foam concentrate | MSC.1/Circ.1432, para.6.2 | |
Annually | Functional test, and taking sample, etc. | MSC.1/Circ.1432, para.7.4 | |
5-yearly | Inspection of each part | MSC.1/Circ.1432, para.9.2 | |
呼吸器 SCBAs | Weekly | Examination of cylinder gauges | MSC.1/Circ.1432, para.4.5 |
Annually | Checking of serviceable condition, etc. | MSC.1/Circ.1432, para.7.8.2 | |
5-yearly | Hydrostatic test | MSC.1/Circ.1432, para.9.4 | |
緊急逃生呼吸器 EEBD | Weekly | Examination of cylinder gauges | MSC.1/Circ.1432, para.4.5 |
Annually | Inspections in accordance with manufacturer’s instructions, etc. | MSC.1/Circ.1432, para.7.8.3 | |
--- | Hydrostatic test | IACS Rec.88 | |
水噴淋系統(tǒng) Water mist, water spray and sprinkler systems | Weekly | Visual inspection, etc. | MSC.1/Circ.1432, para.4.7 |
Monthly | Verification of valves and gauges, etc. | MSC.1/Circ.1432, para.5.4 | |
Quarterly | Assessment of system water quality | MSC.1/Circ.1516, para 6.5 | |
Annually | Blowing air, blowing water test, etc. | MSC.1/Circ.1516, para 7.5 | |
5-yearly | Internal inspection of all control/section valves, etc. | MSC.1/Circ.1516, para 9.3 | |
10-yearly | Hydrostatic test for gas and water pressure cylinders. | MSC.1/Circ.1432, para.10.2 |